Skip to Content

Leon County Non-Compliant Jail Report

Jail Name
Leon County 
Report Date
09/29/2026 
Number of days
22 
Inspector
 
Original Report
Download Non-Compliant Report
Notes and Summary
  • The Ansul Hood Suppression System was found to be red tagged due to the following deficiencies: No gas shutoff present, Excessive grease and debris loading within the plenum, nozzles were not properly aligned, and no electrical shutoff present. Additionally, the standpipe system located in the sally port was found to be yellow tagged for the following deficiencies: Pressure gauges were expired, alarm bell was inoperable, and required five-year maintenance inspection was overdue. All life safety equipment must be maintained in proper working order and remain in compliance with applicable standards. The Ansul Hood and Stand Pipe were repaired the following day 09/17/2026 and kitchen was approved to continue with regular meal service.
  • During the facility walk-through, it was observed that the sanitation conditions within the male inmate worker living areas were below acceptable standards. Excessive amounts of nuisance contraband were found in and around inmate bunks. Additionally, corrosive chemicals were discovered within the housing area, creating a potential safety concern. An excessive quantity of uniforms and linens was also observed, contributing to clutter and poor sanitation practices.
Violation Types
  • Life Safety Rules - Chapter 263: Life Safety
  • Sanitation

Leon County Non-compliant Jail Reports


Back to top