The generator at the annex was identified as having load transfer time greater than the 10 seconds allowed by NFPA Code 110. Transfer time was 21 seconds.
The showers throughout the main jail were observed to have exposed concrete, fruit flies and an unknown black substance on the walls. The shower sanitation issues were a deficiency on the 2018 and 2019 annual inspections. The inspection team also observed sanitation issues in the kitchen including unresolved areas identified from
the 2019 Health Inspection Report
The main jail was indentified to have false secure door indicators on the control board, numerous lights out throughout the facility and several exposed wall joint gaps throughout the facility.
Violation Types
Construction Approval Rules
-
Chapter 257: Construction Approval Rules